Execution standard: enterprise standard
2 use: this product is fit for ac rated voltage up to and including 450/750 of high temperature, corrosive gases and structure requirements within the scope of soft environment is bad place such as the signal transmission and control of the connection.
3 USES features: cable long-term working temperature 60 ℃ ~ 180 ℃. The cable temperature under installation should not below 0 ℃. The bending radius should not less than 6 times of cable diameter.
4 product model and name
Type no.
The name says
KHGG
Copper, silicone rubber insulated and sheathed control cable
KHGPG
Copper core, silicone rubber insulated and sheathed braided shielding control cable
KHGRG
Copper, silicon rubber soft control cable insulation and sheath
KHGP2G
Copper core, silicone rubber insulated and sheathed copper tape screened control cable
KHGRPG
Copper, soft silicone rubber insulated and sheathed woven shielding control cable
KHG20G
Copper, silicon rubber insulation and sheath steel tape armoured control cable
KHPG20G
Copper core, silicone rubber insulated and sheathed woven BingBiGang sheathed control cable
KHG30G
Copper, silicone rubber insulated and sheathed fine steel wire armoured sheathed control cable
5 cable wire core specification and related parameters
Nominal cross section
Mm squared
Conductor structure
Insulation thickness
MM
Dc resistance is not greater than Ω when 20 ℃ / km
2 kinds of
5 kinds of
2 kinds of
5 kinds of
0. 5
7/0.30
16/0.20
0.5
36.0
39.0
0. 75
7/0.37
24/0.20
0.6
24.5
26.0
1. 0
7/0.43
32/0.20
0.6
18.1
19.5
1. 5
7/0.52
30/0.25
0.7
12.1
13.3
2. 5
7/0.68
49/0.25
0.8
7.41
7.98
4. 0
7/0.85
56/0.30
0.8
4.61
4.95
6. 0
7/1.04
84/0.30
0.9
3.08
3.30
Description: silicone rubber insulated control cable core structure for 5 kinds of commonly, if you want to 2 kinds of needs.
6 cable technical performance
6.1 conductor dc resistance should comply with the provisions of the table.
6.2 insulation wire core spark should undergo 5 kv power frequency voltage test.
6.3 the finished insulation resistance of cable should be no less than 500 m Ω · km.
6.4 the finished cable should be able to withstand ac 50 hz, 3000 v / 2 min pressure test.
6.5 2 ~ 37 cable some core, USES the color separation or digital identity.
7 said method, for example:
Silicone rubber insulated and sheathed control cable conductor by the model, some conclusions and the nominal cross section, said, for example, is as follows:
1) silicone rubber insulated and sheathed braided shielding control cable, 7, 1.5 mm squared
Expressed as: KHGPG 7 * 1.5
2) KHG30G: 10 * 2.5 indicates the cable as: silicone rubber insulated and sheathed fine steel wire armoured sheathed control cable, line, some 10 core conductor nominal section 2.5 mm squared
8 the delivery length
Cable length is 100 meters above commonly, delivery length measurement error is not more than plus or minus 0.5%.
According to both sides talks things over, can decide the length of the delivery of the goods.