Heat resistant silicone rubber cable
Heat-resistant silicone rubber insulated cables and heat-resistant silicone rubber sheath flexible cable. Silicone rubber has excellent physical and mechanical properties and electrical insulation properties, resistance to atmospheric aging, smelly endowment, light aging resistant, flame retardant, radiation resistant, oil resistant, is to use one of the highest temperature elastomer material, widely used in Marine cable, aviation wire leads by now, motor, heating cable and other cable insulation and sheath. Heat-resistant silicone rubber cable is suitable for power generation, metallurgy and chemical industry such as high temperature environment and requires heat resistant and corrosion occasion of portable electric equipment such as power, control and signal connection.
1 cable standard
The product enterprise standard Q/ZL196 heat-resistant silicone rubber cable.
2 cable type
Cable type such as table 1. At the same time can produce other structure of the silicone rubber cable according to the requirements of customers.
Table 1
Model name use
YGC v rated voltage 300/500-300/500 heat-resistant silicone rubber cable the electrical connection in the mobile electrical equipment under high temperature and harsh environment
YGC - 600/1000 rated voltage 300/1000 v the electrical connection in the mobile electrical equipment under high temperature and harsh environment
3 cable specification
The standard series of the cable specifications shown in table 2, at the same time can provide other specifications of the cable according to the requirements of customers.
Table 2.
Some nominal section
2
3
4
5 1 ~ 25
1-95
1-95
1 ~ 25
Typical structure diagram below 4 cables.
1-2-3 - insulation conductors fill 4 - sheath
Five main performance index
5.1 the conductor dc resistance (cable conductor dc resistance are shown in table 4).
Table 4
Conductor cross section 20 m ㎡ ℃ conductor resistance Ω/km 20 ℃ maximum conductor resistance m Ω/km minimum value
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95 20.0
13.7
8.21
5.09
3.39
1.95
1.24
0.795
0.565
0.393
0.277
0.210 100
100
100
100
100
100
100
50
50
50
50
50
5.2 insulation resistance
Cable insulation resistance are shown in table 4.
5.3 voltage test
The finished cable shall be subject to the ac voltage test given in table 5.
Table 5
The test voltage kv rated voltage V/min
300/500 2.0/5
600/1000 3.5/5
6 USES features
6.1 the rated working voltage U0 / U are 300/500 and 300/500 v v respectively.
6.2 cable conductor long term allowed working temperature to + 180 ℃.
6.3 the smallest bending radius is six times of cable diameter.